SFW Twin-Compressor Series

Category:

Features

  • Use two or more compressors to perform the cooling function
  • Can maintain the Temperature Accuracy within ± 1˚C (particularly suitable for industries in which precise temperature is needed)
  • Can reduce the Temperature Variation from 3-5˚C (regular chiller) 1˚C
  • Fully utilize the compressors as they will take turns to operate under the control of our specially programmed PCR (Programmable Control Relay)
  • Can lower the start-up current usage and reduce the chance of current surge
Download
  • Cooling Moulds: injection moulding, blow moulding and extrusion
  • CNC Industries: CNC maching center, CNC electrical discharge machine, CNC grinder, CNC Lather
  • Laser Cutting, DI Water Application
  • Electroplating
  • Air pressure spot welder
  • Food Processing
  • machinery using hydraulic oil, lubricating oil or other processing oil

Specification

Model SFW170 SFW200 SFW500 SFW600 SFW840 SFW1000
Cooling Capacity Kcal/hr KW/hr 20640
24
25800
30
40420
47
55040
64
62800
73
86000
100
Compressor Power HP 4 x 2 5 x 2 10 x 2 5 x 2 12 x 2 15 x 2
Water Pump KW
HP
2.2
3
2.2
3
4.1
5.5
4.1
5.5
4.1
5.5
4.1
5.5
Cold Water Flow
Rate  L/min 200 200 350 300 300 300
Head  Meter 25 25 30 42 42 42
Pipe Size (inlet / outlet) Inch 1-1/4 ; 1-1/4 1-1/4 ; 1-1/4 1 1/2 ; 1 1/2 1 1/2 ; 1 1/2 1 1/2 ; 1 1/2 1 1/2 ; 1 1/2
Condenser (inlet / oulet) Inch 1-1/2 ; 1-1/2 1-1/2 ; 1-1/2 2 ; 2 2 ; 2 2 ; 2 2 ; 2
Dimension Length mm
Width mm
Height mm
1255
722
1305
1255
722
1305
1580
900
1500
1780
900
1630
1850
1030
1500
1850
1030
1500
S/S Water Tank Volume Litre 140 140 180 330 330 330